Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features.

The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type A & AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Includes a phase sequence indicator
  • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

A solid, reliable, basic installation tester

  • Tests voltage and frequency
  • Checks wiring polarity to detect broken N wires
  • Measures insulation resistance and loop and line resistance
  • Measures motor windings with continuity test
  • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)

Specifications:

AC voltage measurement:

  • Range: 500 V
  • Resolution: 0.1 V
  • Accuracy 45 Hz – 66 Hz: 0.8% + 3
  • Input impedance: 360 kΩ
  • Overload protection: 660 V rms

Continuity testing (RLO):

  • Range (autoranging): 20 Ω / 200 Ω / 2000 Ω
  • Resolution: 0.01 Ω / 0.1 Ω / 1 Ω
  • Open Circuit Voltage: >4 V

Insulation resistance measurement (RISO):

  • Accuracy of tTest voltage (at rated test current): +10%, -0%
  • Test voltage:
    • 100 V
    • 250 V
    • 500 V
    • 1000 V
  • Insulation resistance range:
    • 20 MΩ / 50 MΩ
    • 20 MΩ / 100 MΩ
    • 20 MΩ / 200 MΩ
    • 20 MΩ / 200 MΩ / 500 MΩ
    • 20 MΩ / 200 MΩ / 1000 MΩ
  • Resolution:
    • 0.01 MΩ / 0.1 MΩ
    • 0.01 MΩ / 0.1 MΩ
    • 0.01 MΩ / 0.1 MΩ
    • 0.01 MΩ / 0.1 MΩ / 1 MΩ
    • 0.01 MΩ / 0.1 MΩ / 1 MΩ
  • Test current:
    • 1 mA @ 50 kΩ
    • 1 mA @ 100 kΩ
    • 1 mA @ 250 kΩ
    • 1 mA @ 500 kΩ
    • 1 mA @ 1 MΩ

Loop and line impedance (ZI):

  • Range: 10 Ω / 0.001 Ω / High current mΩ mode
  • Resolution: 0.01 Ω / 0.1 Ω / 1 Ω

Prospective earth fault current, PSC test:

  • Range: 1000 A / 10 kA (50 kA)
  • Resolution: 1 A / 0.1 kA
  • Computation: Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.

RCD testing, RCD types tested:

  • RCD Type: A4, AC¹, G², S³
  • Notes:
    • 1 Responds to AC
    • 2 General, no delay
    • 3 Time delay
    • 4 Responds to pulsed signal
    • 5 Responds to smooth DC signal

Tripping speed test (ΔT):

  • Current settings¹:
    • 10-30-100-300-500-1000 mA – VAR
    • 10-30-100 mA
  • Multiplier:
    • x ½, x 1
    • x 5
  • Measurement range:
    • RCD Type G: 310 ms, 50 ms
    • RCD Type S: 510 ms, 160 ms
  • Notes:
    • ¹1000 mA type AC only
    • 700 mA maximum type A in VAR mode
    • VAR mode not available for type B.

RCD/FI-Tripping Current Measurement/Ramp Test (IΔN):

  • Current range: 30% to 110% of RCD rated current¹
  • Step size: 10% of IΔN²
  • Dwell time:
    • Type G - 300 ms/step
    • Type S - 500 ms/step
  • Measurement accuracy: ±5%
  • Specified trip current ranges (EN 61008-1):
    • 50% to 100% for Type AC
    • 35% to 140% for Type A (>10 mA)
    • 35% to 200% for Type A (≤10 mA)
    • 50% to 200% for Type B
    • 25% for Type B
  • Notes:
  • ¹30% to 150% for Type A IΔN > 10 mA
  • 30% to 210% for Type A IΔN = 10 mA
  • 20% to 210% for Type B

Phase Sequence Indication:

  • Icon: icon phase sequence indicator Phase Sequence indicator is active.

General Specifications:

  • Size (L x W x H): 10 x 25 x 12.5 cm
  • Weight (incl. batteries): 1.3 Kg
  • Battery size, quantity: Type AA, 6 ea.
  • Sealing: IP-40
  • Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
  • Overvoltage: CAT III / 500V; CAT IV 300V
  • Performance: EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

Includes:

  • 6x AA (IEC LR6) cell batteries
  • C1600 hard carrying case
  • Zero adapter
  • Heavy duty mains cord
  • STD standard test lead set
  • C1600 hard carrying case
  • Padded carrying and waist strap
  • Quick reference guide
  • TP165X remote control probe and lead
  • User's manual on CD-ROM
Specification
Part No FLU1662
Barcode 95969766821
Brand Fluke
Product Length (mm) 100
Product Width (mm) 250
Product Height (mm) 125
Voltage 1000V